While receiving Bulk LPG
    Only authorised personnel should be permitted to enter into the LPG yard
    Always ensure proper earthing connections to the mobile LPG tanker before unloading operation
    Do not engage damaged / leaky hoses for unloading the tanker
    Replace gasket whenever unloading of LPG tanker takes place
    Do not carry out unloading operation during night time , Heavy rains, Thunder storms, Lighting etc
    Always tighten all fasteners of the LPG unloading hoses fully to the mobile tanker
    Do not overfill the LPG storage tank beyond the maximum filling limit of 85%
    Ensure hoses are depressurized prior to disconnecting from the tanker
Out of LPG
    Turn off the main stop valve
    Make sure all appliances are turned off
    After delivery, the Under Pressure Shut Off (UPSO) valve (where fitted)
    Should be reset
LPG Operations
    All LPG operations must be carried out by personnel well trained in LPG operations
    Maintain good housekeeping inside the LPG yard. Remove all dry vegetation and other flammable materials
    Avoid all sources of ignition and make sure the “No Smoking” signs and other Safety signage’s are displayed
    Care should be taken when draining water (present if any) from storage tank in order to prevent escape of LPG/Propane/ Butane
Maintenance
    Before carrying out any maintenance work, a work permit shall be obtained
    All maintenance operations inside the LPG yard must be carried out by authorised service personnel only
    No hot work like welding, cutting, heating shall be carried inside the LPG installation (fenced area)
    All maintenance work for burners or combustion system should be carried out through authorised Indane service provider’s personnel
Safe Operation of LPG Installation
    There should be No Smoking and No Ignition Sources near the LPG vessel
    Do Not Allow rubbish or flammable materials to accumulate around the LPG vessel
    Keep foliage from growing around or over the LPG vessel
    Do not paint the LPG vessel or obscure any signs or labels attached to it
    Keep access to the LPG vessel free at all times
    Arrange for regular servicing of all your LPG appliances including flues
    If the premises are to be Left Unattended for a long period, Turn off the gas supply at the Emergency Stop Valve
    Any Faults or Damage to the LPG vessel should be reported to IOC Ltd
Vessel Safety System

Your installation may be fitted with one of two safety systems, Type A or Type B. Both are designed to guarantee the safe supply of LPG to your premises.

Over Pressure Shut Off Valve (OPSO)
This will isolate the supply and protect against excess pressure affecting the appliances. Should this device operate it should NOT be reset without the advice of a competent person as there may be a potential serious fault.

Under Pressure Shut Off Valve (UPSO)
This device will isolate the gas supply should there be a reduction in pressure and may be reset by you. For example if the tank has been allowed to empty or if the gas supply has been turned off at the main stop valve

In case of Leakage
    Should a gas leak occur, it is likely that it will be first noticed by the smell
    Do not Panic
    Isolate LPG supply from the LPG yard
    Stop all LPG Operations
    Turn off the supply at emergency and main stop valves
    Extinguish all naked lights and sources of ignition - NO SMOKING
    Open doors and windows. Beware that LPG is heavier than air and will collect at the lowest levels
    Do not SWITCH electrical appliances on or off – NO MOBILE PHONES
    Activate emergency management plan
    Contact your Inane Bulk Service Provider/ installer for internal leakages and appliance problems and IOCL Officials & Supplier in the event of an external leakage for Help
In case of Fire
    Evacuate the building
    Call the fire brigade
    Turn off the gas supply at the emergency stop valve if it is safe to do so
    Advise the Fire Officer of the existence of an LPG bulk storage tank
    Contact IOCL
Please note that IOCL & Suppliers’ Technicians are only certified for working with external equipment - the vessel, pipe work and associated gauges and connectors

In Case of any Doubt Please Contact your Inane Bulk Service Provider/ installer for internal leakages and appliance problems and IOCL Officials & Supplier in the event of an external leakage for Help
To refill your cylinder fill the form and get your booking No.
To refill your cylinder fill the form and get your booking No.
To refill your cylinder fill the form and get your booking No.
Book your cylinder by SMS
Book your cylinder Online
view our ISO Certification ...
Home  |   Management Structure  |    CSR  |    Production Figure  |    Sitemap  |    Feedback  |   Contact Us
Site best viewed by 1024 x 768 resolution and above, Site designed and developed by Micro Research Associates

Contact: Mr. Bijan Behari Biswas, Ph. 9830064144
E-mail : bijanbb@yahoo.com, bijanbb@gasandgadgets.com